ENMET Corporation PO Box 979 Ann Arbor, MI 48106-0979 Manual Part Number 80003-501 MCN-423, 07/15/09 CP-60 OPE
CP-60 ENMET Corporation 7 3.4.2 Relay Contacts Auxiliary alarms should be powered from an independent power source separate form the instrument p
CP-60 ENMET Corporation 8 4.0 Operation 4.1 Normal Operation Condition With the CP-60 installed as described in Section 3, and in clean air, the P
CP-60 ENMET Corporation 9 4.5 Display In clean air a display is shown in Figure 4. This position of the display is termed the "operational d
CP-60 ENMET Corporation 10 5.0 Maintenance The CP-60 has no specific preventative maintenance requirements. Entering the maintenance menu, as out
CP-60 ENMET Corporation 11 5.2.1 Set 4 –20mA Transmitter Scale This section of the maintenance menu is for external sensor/transmitters. This fu
CP-60 ENMET Corporation 12 5.2.2 Set Alarm Points Factory alarm set points are discussed in Section 4.2, See Table 1. To change the alarm points
CP-60 ENMET Corporation 13 Example: Set Alarms Flow Chart Displays shown are factory default settings. Λ - Indicates alarm triggered on increasing
CP-60 ENMET Corporation 14 5.2.3 Set Alarm “Delay On” The alarms may be set to delay activation by 1 second increments, from 1 to 30 seconds. WARN
CP-60 ENMET Corporation 15 5.2.5 Failsafe Configuration The CP-60 is factory set in a failsafe configuration. This means that if power is discon
CP-60 ENMET Corporation 16 5.2.7 Set New Password To change the password, you must enter the maintenance menu. Press the OPTION switch until “Ent
Table of Contents 1.0 Introduction ...
CP-60 ENMET Corporation 17 6.0 Technical Data and Specifications The technical data and specifications of the CP-60 instrument. Electrical Power 1
CP-60 ENMET Corporation 18 8.0 WARRANTY ENMET warrants new instruments to be free from defects in workmanship and material under normal use for a
PO Box 979 680 Fairfield Court Ann Arbor, Michigan 48106-0979 734.761.1270 Fax 734.761.3220 Returning an Instrument for Repair ENMET instrumen
Repair Return Form Mailing Address: ENMET Corporation PO Box 979 Ann Arbor, Michigan 48106 Phone Number: 734.761.1270 FAX Number: 734.
List of Figures Figure 1: CP-60 External Features ...
CP-60 ENMET Corporation 1 1.0 Introduction The CP-60 control panel is capable of monitoring from 1 to 3 remote sensors. Some features of the moni
CP-60 ENMET Corporation 2 2.0 Instrument Features 2.1 CP-60 Exterior Features The exterior of the instrument is shown in Figure 1. The exterior f
CP-60 ENMET Corporation 3 2.3 Circuit Board Features The Display Panel is hinged on the left and is released by unscrewing the 2 philips screws lo
CP-60 ENMET Corporation 4 3.0 Installation 3.1 Mounting of Instrument Mount the CP-60 instrument on an appropriate vertical surface using the moun
CP-60 ENMET Corporation 5 3.4 Sensor/Transmitter Connection Sensor/Transmitters are connected to the CP-60 control unit with two or three-conducto
CP-60 ENMET Corporation 6 3.4.1 Outputs Two types of alarm outputs are available, relay contacts and 4-20mA outputs. Figure 5: CP-60 Relay, Inpu