ENMET Corporation PO Box 979 Ann Arbor, MI 48106-0979 www.enmet.com Manual Part Number 80003-098 MCN-13-011, 12/20/13 E
EX-5155-MOS ENMET Corporation 8 5.0 Maintenance of the EX-5155-MOS CAUTION: Do not open the EX-5155-MOS S/T in a classified area. CAUTION: Do Not
EX-5155-MOS ENMET Corporation 9 5.2 Calibration of the EX-5155-MOS Calibration is the process of setting the instrument up to read accurately when
EX-5155-MOS ENMET Corporation 10 Table 3: Examples of Standard and Non-Standard Calibration Gas Gas Range Alarm 1* Alarm 2* Alarm 3* Sensor
EX-5155-MOS ENMET Corporation 11 5.2.1 Zero Adjust A ZERO function should be performed only when the EX-5155-MOS sensor/transmitter is exposed to
EX-5155-MOS ENMET Corporation 12 Normal Display Mode 5ppm MENU HOLD the magnet over the MENU switch for 2 – 4 seconds to enter the Maintenanc
EX-5155-MOS ENMET Corporation 13 Figure 5: EX-5155-MOS Maintenance Menu Flow chart 5.3 Heater Voltage Settings Heater Voltages are necessary for
EX-5155-MOS ENMET Corporation 14 6.0 Replacement Part Numbers ENMET replacement part numbers: Description Part Number For EX-5155-MOS p/n 10014-0
EX-5155-MOS ENMET Corporation 15 Addendum: Ammonia Calibration Calibration Procedure for EX-5155-MOSAmmonia The EX-5155-MOSAmmonia sensor requires
PO Box 979 680 Fairfield Court Ann Arbor, Michigan 48106-0979 734.761.1270 Fax 734.761.3220 Returning an Instrument for Repair ENMET instru
Repair Return Form Mailing Address: ENMET Corporation PO Box 979 Ann Arbor, Michigan 48106 Phone Number: 734.761.1270 FAX Number: 734
Table of Contents 1.0 INTRODUCTION ...
EX-5155-MOS ENMET Corporation 1 1.0 Introduction The ENMET EX-5155-MOS sensor/transmitters (S/T) is a 3-wire, 24 VDC 4-20mA S/T for the detectio
EX-5155-MOS ENMET Corporation 2 2.0 Features of the EX-5155-MOS See Figure 1 for location of features: Feature Description Display LCD: Indicate
EX-5155-MOS ENMET Corporation 3 3.0 Installation of the EX-5155-MOS CAUTION: Area must be declassified during installation. The ENMET EX-5155-MOS
EX-5155-MOS ENMET Corporation 4 3.2 Wiring the EX-5155-MOS to a Control Unit CAUTION: Area must be declassified during installation. Run conduit
EX-5155-MOS ENMET Corporation 5 Figure 3: Terminal Positions EX-5155-MOS Sensor/Transmitter When wiring is complete, reassemble the EX-51
EX-5155-MOS ENMET Corporation 6 4.0 Operation of the EX-5155-MOS It is best to have the EX-5155-MOS transmitters powered up and operational for 24
EX-5155-MOS ENMET Corporation 7 Purge times vary form 5 – 25 minutes depending on the sensor installed. Some sensors require additional purge time